Name
Range
Step Default Prot.funcs.
Description
Min
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
3.5xI
n
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting defines
the current limit for when this current is exceeded while the
automatic curve selection and the control only short time
constant (stall) are in use.
Min
locked
rotor
current
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's minimum locked rotor current. This setting defines
the current limit for when this current is exceeded while the
automatic curve selection and the control only short time
constant (stall) are in use.
Max
locked
rotor
current
0.1…40.0xI
n
0.1xI
n
7.5xI
n
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
Maximum locked rotor current of the motor. This setting defines
the current limit which is maximum current for the motor to
draw in locked rotor situation (starting or stalled). If the
measured current exceeds this setting limit it is considered to
be overcurrent fault and corresponding measures can be
applied to disconnect the feeder and motor from the supply.
Max
locked
rotor
current
A
0.1...5
000.0A
0.1A
-
- Motor
status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The maximum locked rotor current in amperes.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
247