Programming a Point’s Software Point Type,
Continued
7-10
Category
Point Type
Application
Control
AHUF
AHU OFF Relay (Dual Relay Control)
AHUO
AHU ON Relay (Dual Relay Control)
AHUR
AHU ON/OFF Relay (Signal Relay control)
ALTERN
Alternate Elevator Capture
BSIGNAL
Trouble/Supervisory Bell Signal (on until ACK)
DHOLDER
Door Holder Control
PRIMARY
Primary Elevator Capture
RELAY
Generic Relay
RELISIG
Releasing investigation signal (NYC abort
operation).
RELSIG
Suppression release audible signal (Temporal on
first alarm; 120 bpm on hazard alarm (delay timers
active); steady on release; off on silence).
RELVIS
Suppression release visual signal (on when
releasing output activates; off on reset).
RELWVIS
Releasing warning visual circuit (on when alarm
occurs in hazard area; off on reset).
RSIGNAL
Alarm Signal (on until reset)
RVISUAL
Visual (on until reset)
RWATER
Waterflow Signal (on until reset)
SIGNAL
Generic Signal (no default operation)
SSIGNAL
Alarm Signal (on until silence)
SUPREL
Suppression (Agent Discharge) Release Output
SUPV
Sprinkler Supervisory Signal (on until ACK)
24 Point I/O
LAMP
Lamp Output
OSWITCH
2-position switch (open, supervised)
PIEZO
Piezo output
RELAY
Generic Relay
RRELAY
Relay (on until reset)
SSWITCH
2-position switch (open/short supervised)
TSWITCH
3-position switch (open, supervised)
USWITCH
2-position switch (unsupervised)
Table 7-3. Point Types,
continued