Table A-13. Digital Pseudo Points
Point
Type
Label
Description
D1
R U
Unacked Fire
in System
On if unacked fire exists in system.
D2
R U
Unacked
Supervisory
in System
On if unacked supervisory exists in system.
D3
R U
Unacked
Trouble in
System
On if unacked trouble exists in system.
D4
R T
Extra N2
Card
Turned on at panel startup if an unprogrammed
N2 slave card is detected. Only clears on panel
restart.
D5
R T
External N2
Trouble
Turns on when panel is no longer communicating
with ALL slave cards. Turns off on a System
Reset.
D6
RW U
User SMPL
Program
On when User SMPL program is active.
D7
R T
Cold Start
Indicates that panel has performed a cold start.
Turns of when acknowledged.
D8
R T
Warm Start /
Check Time
and Date
Indicates that panel has performed a warm start.
Turns off when acknowledged.
D9
RW
F
Manual
Evacuation
Turns on when Manual Evacuation is selected.
Turns off on a System Reset.
D10
R T
System Time
and Date
Indicates that the time and date is incorrect.
Turns off when time and date is updated.
D11
R T
Service
Mode
Indicates that the panel is in Service Mode.
Turns off only on a panel restart.
D12
RW U
Keypad
Inactivity
Timer
Disable
Disables Keypad Inactivity timer.
D13
R T
Active List
Overflow
Turns on when the number of alarms,
supervisories, or troubles is greater than the
system active list size (50 fires, 50 supv, 100