11-3
Downloading a CFIG File to the Panel
Overview
This section describes downloading a CFG file (built job file) from a service PC to the
AUTOPULSE Z-28 FACP. A download occurs over a serial link running between the panel
and the PC. Follow the steps outlined in the following sections to link the PC to the panel and
download the job.
Step 1. Set Panel and PC
Serial Communication
Parameters
1.
Set switches SW1 and SW2 to the positions shown in Figure 11-2. These positions enable
a baud rate of 19,200 on the AUTOPULSE Z-28 FACP.
Figure 11-2. Switch Position for 19,200 Baud
2.
Start the AUTOPULSE Z-28 Programmer application.
Click on the Transfer menu and select Settings. A dialog similar to the one shown in Fig-
ure 11-3 appears.
Figure 11-3. Setting PC Transfer Rate to 19,200
3.
Set the parameters in this dialog as follows:
•
Port. Set this radio button to the setting that corresponds to the serial port on the PC
to which the serial cable will be connected. In most cases, this will be COM1.
•
Baud Rate. Set to 19,200.
•
Parity. Set to None.
•
Stop Bits. Set to 1.
•
Data Bits. Set to 8.
Continued on next page
Black indicates switch position
19,200
Black indicates switch position.