Addresses for Pseudo Points,
Continued
A-27
Continued on next page
Point
Type
Label
Description
D14
RW
T
City
Disconnect
On if city circuit is disconnected.
D15
R T
City Circuit
Trouble
On if city circuit is in trouble.
D16
RW U
AHJ City
Reset
During a system reset, if this pseudo is On, a
point will reset unless it is in an ALARM state. A
point has to be in a NORMAL state to reset, when
the AHJ pseudo is off.
D17
RW
T
Control Point
Bypass
On if control points are bypassed.
D18
RW
T
Elevator
Bypass
On if elevator recall points are bypassed.
D19
RW
T
Doorholder
Bypass
On if doorholder points are bypassed.
D20
RW
T
Verification
Tally Limit
Exceeded
On when any verified point’s tally limit exceeds
10. Off when all points tally limit is below 10.
D21
R T
Walk Test
Active in
System
On when Walk Test is active.
D22
R U
Earth Fault
Latch
On when Earth Fault Latch diagnostic is active.
D23
R T
SIMtest
Active in
System
On when SIMtest is active.
D24
R T
Programming
Mode -
System
Disabled
On when Programming or Quick-CFIG is entered.
Panel is no longer operational.
D25
RW U
System
Reset
Activated
This point is turned on when a system reset is
initiated. The point may be turned off using
SMPL.
D26
RW U
Alarm
Silence
Activated
This point is turned on when an alarm silence is
initiated. The point may be turned off using
SMPL.
Table A-13. Digital Pseudo Points
, continued