Step 4. Edit An Output Statement’s Properties,
Continued
10-20
Continued on next page
Opcode
Qualifier
Application
Set Heat
Threshold
117°
Fahrenheit
When the input side of the equation is true, the threshold level for the heat
detector is set to 117 degrees F.
135°
Fahrenheit
When the input side of the equation is true, the threshold level for the heat
detector is set to 135 degrees F.
155°
Fahrenheit
When the input side of the equation is true, the threshold level for the heat
detector is set to 155 degrees F.
Set ROR
3° C / minute
When the input side of the equation is true, the threshold level for the ROR heat
detector is set to 3° C / minute.
15° F /
minute
When the input side of the equation is true, the threshold level for the ROR heat
detector is set to 15° C / minute.
20° F /
minute
When the input side of the equation is true, the threshold level for the ROR heat
detector is set to 20° C / minute.
Set ION
Threshold
Smoke Level
0.5
When the input side of the equation is true, the threshold level for the ION
smoke detector is set to 0.5.
Smoke Level
0.9
When the input side of the equation is true, the threshold level for the ION
smoke detector is set to 0.9.
Smoke Level
1.3
When the input side of the equation is true, the threshold level for the ION
smoke detector is set to 1.3.
Smoke Level
1.7
When the input side of the equation is true, the threshold level for the ION
smoke detector is set to 1.7.
Set
XPHOTO
Threshold
Smoke Level
0.2
When the input side of the equation is true, the threshold level for the extra-
sensitive photo smoke detector is set to 0.2.
Smoke Level
0.5
When the input side of the equation is true, the threshold level for the extra-
sensitive photo smoke detector is set to 0.5.
Smoke Level
1.0
When the input side of the equation is true, the threshold level for the extra-
sensitive photo smoke detector is set to 1.0.
Smoke Level
1.5
When the input side of the equation is true, the threshold level for the extra-
sensitive photo smoke detector is set to 1.5.
Smoke Level
2.0
When the input side of the equation is true, the threshold level for the extra-
sensitive photo smoke detector is set to 2.0.
Smoke Level
3.0
When the input side of the equation is true, the threshold level for the photo
smoke detector is set to 3.0.
Smoke Level
3.7
When the input side of the equation is true, the threshold level for the photo
smoke detector is set to 3.7.
HORN OFF
Used with NACnet Non-Addressable Horns. When the input side of the
equation is true, Horn OFF turns NACnet Non-Addressable horns off.
Table 10-2. Output Opcodes and Qualifiers
, continued