6-35
Programming a 24 Point I/O Card,
Continued
Programming an Output
Point
1.
Click on the Device Type field and select the GRAPHOUT device type.
2.
Click on the point type field and select one of the following:
•
LAMP. Specifies that the output is an LED.
•
PIEZO. Specifies that the output is an audible piezo device. Piezo beeps to indicate
an alarm, and sounds a steady tone to indicate a trouble or supervisory condition.
•
RELAY. Specifies that the output is a generic relay.
•
RRELAY. Specifies that the output is a relay that activates upon ALARM and turns
OFF upon reset.
3.
Select the mode (operation) of the output. Refer to Table 6-15 for specific information on
the modes.
4.
Click on the Ref Addr field and select the point used to trigger the output.
Table 6-13. Output Device Modes
Mode
Application
DISABLE
Output activates when the referenced point is Disabled.
FIRE
Output activates when the state of the referenced point is in an
ALARM condition.
LF
Output activates when any Alarm condition occurs.
LS
Output activates when a Supervisory condition occurs.
LT
Output activates when a Trouble condition occurs.
OFF
Output activates when the state of the referenced point is OFF.
ON
Output activates when the state of the referenced point is OFF.
SMPL
Output activates when a Custom Control equation executes.
SUPERV
Output activates when a Supervisory condition occurs to the
referenced point.
TROUBLE
Output activates when a Trouble condition occurs to the
referenced point.