Monitor Point Types,
Continued
A-11
SFIRE
Used when smoke detectors and shorting type devices are connected to an IAM or ZAM.
VFIRE
Used to activate the alarm verification software for all smoke detectors connected to an IAM or
ZAM. Shorting type devices cause an immediate alarm.
SPULL
Used when smoke detectors and pull stations are connected to an IAM or ZAM.
VSPULL
Used when smoke detectors that must be verified and pull stations are connected to an IAM or
ZAM.
Continued on next page
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Monitor Zone
Smoke Alarm
Open
Fire Monitor Zone
Open Trouble
Short
Fire Monitor Zone
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Monitor Zone
Verified Alarm
Open
Fire Monitor Zone
Open Trouble
Short
Fire Monitor Zone
Fire Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Monitor Zone
Smoke Alarm
Open
Fire Monitor Zone
Open Trouble
Short
Fire Monitor Zone
Manual Alarm
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Monitor Zone
Verified Alarm
Open
Fire Monitor Zone
Open Trouble
Short
Fire Monitor Zone
Manual Alarm