Monitor Point Types,
Continued
A-12
GENMON
Used when emergency generator monitoring is required. The shorted condition of the circuit
indicates an abnormal status and is indicated by the Supervisory Service LED. The current
limited condition of the circuit indicates that the generator is running, and can be tracked with
an LED (must be programmed). A current limiting resistor must be installed for this to
happen.
SGENMON
Same operation as the GENMON point type, but the generator running condition automatically
displays and requires operator acknowledgment.
FPUMP
Used to monitor fire pump conditions. The shorted condition indicates that the fire pump is
abnormal. The current limited condition indicates that the fire pump is running.
SFPUMP
Same as the FPUMP point type, except that the fire pump running condition requires operator
acknowledgment.
Continued on next page
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Generator Monitor
Running
Open
Generator Monitor
Open Trouble
Short
Generator Monitor
Abnormal
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Generator Monitor
Running
Open
Generator Monitor
Open Trouble
Short
Generator Monitor
Abnormal
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Pump Monitor
Running
Open
Fire Pump Monitor
Open Trouble
Short
Fire Pump Monitor
Abnormal
Circuit Status
LCD Display
System Status
Normal
Normal
Limited
Fire Pump Monitor
Running
Open
Fire Pump Monitor
Open Trouble
Short
Fire Pump Monitor
Abnormal