Addresses for Pseudo Points,
Continued
A-30
Z-28 System Analog
Psuedos,
continued
AUTOPULSE Z-28
User
Analog Pseudos
The user analog pseudo card in the AUTOPULSE Z-28 is at address 21. It has 25 points
available for specialized applications programming. The analog user pseudos can have custom
Continued on next page
labels assigned to them.
Table A-14. Analog Pseudo Points
Point
Label
Description
A1
Fire Count
Number of fire alarms active in system.
A2
Supervisory
Count
Number of supervisory alarms active in system.
A3
Trouble
Count
Number of troubles active in system.
A4
System
Startup
Pulsed for one poll cycle during system startup.
A5
Almost Dirty
Device Count
Total number of devices that have an almost dirty status
(not necessarily a trouble).
A6
Dirty Device
Count
Total number of devices that are in Dirty Trouble.
A7
Excessively
Dirty Device
Count
Total number of devices that are in Excessively Dirty
Trouble.
A8
Current Year
Numeric representation of the current calendar year.
(Example: the year 2002 is shown as 02).
A9
Current
Month
Numeric representation of the current calendar month
(1 - 12).
A10
Current Day
Numeric representation of the current calendar day.
A11
Current Hour
Current hour (0 - 23).
A12
Current
Minute
Current minute (0 - 59).