Control Point Types,
Continued
A-6
RELVIS
Suppression release visual signal. ON when agent is released; OFF on reset.
RELWVIS
Pre-suppression release visual warning signal. ON during first stage alarm, delay countdown,
or agent release; OFF on reset.
RSIGNAL
Alarm signal - on until reset. Used for any signaling device (such as an audible or visible
notification appliance) that is required to be on until a system reset is performed. Points
assigned with this type operate on general alarm.
RVISUAL
Used only with visual notification appliances that must be ON until a system reset is
performed. Points assigned with this type operate on general alarm.
Continued on next page
Circuit Status
LCD Display
System Status
ON
Release Visual
ON
OFF
Release Visual
OFF
Release Visual
CODING
Disabled TBL
Release Visual
TROUBLE
OFF AUTO TBL
Release Visual
TROUBLE
Circuit Status
LCD Display
System Status
ON
Releasing Warning
ON
OFF
Releasing Warning
OFF
Releasing Warning
CODING
Disabled TBL
Releasing Warning
TROUBLE
OFF AUTO TBL
Releasing Warning
TROUBLE
Circuit Status
LCD Display
System Status
ON
Signal Circuit
ON
OFF
Signal Circuit
OFF
Signal Circuit
CODING
Disabled TBL
Signal Circuit
TROUBLE
OFF AUTO TBL
Signal Circuit
TROUBLE
Circuit Status
LCD Display
System Status
ON
Visual
ON
OFF
Visual
OFF
Visual
CODING
Disabled TBL
Visual
TROUBLE
OFF AUTO TBL
Visual
TROUBLE