Installation Procedures: 17" Panels
77
VG-Series Modero Touch Panels
Installation of an NXD-1700VG
The NXD-1700VG can be installed either directly into the (optional) CB-TP17 or other solid surface
environment using the two different mounting options: drywall clips or solid surface screws. The
following sections describe mounting the touch panel directly into an installed pre-wall Conduit Box, a
solid surface or drywall, and optional NXA-RK17 Rack Mount Kit.
Installing the NXD-1700VG within a CB-TP17 Conduit Box
The conduit box must be mounted prior to continuing this section. Refer to the procedures in the
Pre-wall Installation of the CB-TP17 Conduit Box
section on page 75 for detailed pre-wall installation
instructions. Verify that all necessary cables have been threaded through the knockouts on the conduit
box and the connections have been tested prior to installation of the NXD-1700VG.
1.
Remove the magnetic faceplate/bezel (
A
in
FIG. 57) from the main NXD unit (
B
in
FIG. 57) by
gripping the faceplate and pulling with gentle outward force.
2.
Verify the incoming RJ-45, Ethernet, and any other audio/video cables have been properly threaded
through the wiring knockouts on the left of the conduit box. Leave enough slack in the wiring to
accommodate any re-positioning of the panel.
3.
Connect all data and power wiring connectors to their corresponding locations along the side of the
(un-powered) NXD touch panel.
Verify the terminal end of the power cable is not connected to a power supply before plugging
in the 2-pin power connector.
The USB connectors can be from either a USB extension cable, or a wireless USB RF
transmitter.
FIG. 56
Screw locations for conduit box attachment in a pre-wall installation
Notched stud
Knockouts should be located on
Inserted block bridges the gap
Stud fastening holes
Mounting tabs for
NXD Wall Mount panel
Use four #8 flat-head
should be flush
with the outside
Stud
of the sheetrock
Mounting Screws to secure
the NXD to the CB
Conduit Box can be
fastened to both
studs)
between the Conduit Box and
the notched beam
Secure Beam to block
Depth depends on the
thickness of the Drywall
Drywall/sheetrock
the left-side of the conduit box,
alongside the connectors
Summary of Contents for Modero NXT-1500VG
Page 4: ......
Page 62: ...Touch Panel Accessories 52 VG Series Modero Touch Panels...
Page 100: ...Installation Procedures 17 Panels 90 VG Series Modero Touch Panels...
Page 178: ...Firmware Pages and Descriptions 168 VG Series Modero Touch Panels...
Page 250: ...Appendix 240 VG Series Modero Touch Panels...
Page 251: ...Appendix 241 7 Modero Widescreen Touch Panels...