Axpert-Eazy
AC Variable Frequency Drive
6-53
6
Acceleration
time-1 (A201)
Deceleration
time-1 (A202)
Max. Frequency (A103)
F
t
A206
A206
A207
A207
A208: Current Limit Acceleration Time (Sec)
A209: Current Limit Deceleration Time (Sec)
These are the acceleration / deceleration time for the stall current limit function. When the AC DRIVE
is operating at set frequency and output current exceeds the stall current limit
B301
value, the output
frequency and voltage are reduced. The deceleration time is decided by current limit deceleration time
A209
. The dc bus voltage will rise in this process. If DC bus voltage control (
B307= 2 or 3
) is enabled,
it will stop the deceleration, if dc bus voltage exceeds 740 Vdc level for 400 V series. This level is
factory settable. The deceleration will resume, if dc link voltage reaches to 710 V (hysteresis of 30 V)
and the output current is still higher than the stall current limit. When the output current falls below the
stall current limit, the output frequency and output voltage will ramp up with current limit acceleration
time
A208
to set frequency value. The dc bus regulation level for 500 V series is 875 Vdc and 1050
Vdc for 600 V series.
Current Limit
Decel Time (A209)
Current Limit Accel
Time (A208)
Vdc
F
I
Output Freq.
(M101)
Stall Current
Limit (B301)
t
t
t
DC Bus voltage Control
(B307=2 or 3)
740Vdc
M105
A210: Acceleration Deceleration Multiplier
This is multiplier for the acceleration/ deceleration time related parameters. Parameters A201 ~ A207
and D206 ~ D207 will be multiplied by this multiplier and the effective values of these parameters will
be the result of this multiplication.
For example, if A201=10 second and A210=10, then the effective value of A201=100 second.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...