Amtech
A.4
13
A
O
p
e
ra
ti
o
n
S
p
e
c
if
ic
a
ti
o
n
s
Digital outputs
4-Programmable Sequence Outputs, open collector type
Programmable to 40 different options: Not Used, Run, Local, Reverse Run, I-Detection, Freq Attain, Speed
Detect1, Speed Detect2, Acceleration, Deceleration, Aux Drive, Timer Output, Zero Speed, Fault Alarm, PID
Up Limit, PID Lo Limit, Temp Alarm, Ready, Pump-1, Pump-2, Pump-3, Pump-4, Doff-End Alarm, Sleep
Mode, Fault, PLC Output 1, PLC Output 2, PLC Output 3, PLC Output 4, PLC Output 5, PLC Output 6, PLC
Output 7 PID F/B ULmt, PID F/B LLmt, Fan Control, Ready1, MBRK, KEB ON, STO Feedback and Panel
Temperature Alarm
Potential Free Contacts
3-Programmable relays:
1-NO, 1-NC for 2A @ 240 VAC
Programmable to 40 different options same as digital outputs
Programmable Analog
Outputs
2-Programmable analog voltage outputs VO1 & VO2: 0~10 Vdc
2-Programmable analog current outputs IO1 & IO2: 4~20 mA
Programmable between 15 different options: Output Frequency, Output Current, Output Power, Output
Voltage, DC Bus Volt, PID Output, Heat sink temperature, PLC Analog Output 1, PLC Analog Output 2, PLC
Analog Outpu3, PLC Analog Output 4, Unipolar Torque Current, Excite Current, Set Frequency and Bipolar
Torque Current
Network connectivity
RS-485 for PC Interface with Modbus-RTU protocol as standard
Auto Restart
Adjustable up to 10 times for ten faults
PID Controller
Inbuilt PID can be used as stand alone
D
is
p
la
y
Display and Keypad unit
Total 80-Character, 4-Line LCD panel with backlit, 8-Key keypad, 3-Status indicating LED for Run, Stop and
Fault.
Simultaneous display of eight selectable monitor parameters from Output frequency, RPM, Current, %
Current, Set frequency, PID Reference, PID Feedback, Input voltage Vry, Input voltage Vyb, Output voltage,
DC Bus voltage, kW, kWH, MWH, Heat sink temperature °C and °F, Set Torque, Torque Current, Excitation
Current, ASR O/P Monitor and ACR O/P Monitor
P
ro
te
c
ti
v
e
S
p
e
c
if
ic
a
ti
o
n
s
Protective Function
Current Limit, Over current fault, Drive over load fault, Motor over load fault, Load side short circuit fault,
Under current fault, DC Bus Over voltage fault, DC Bus Under voltage fault, Temperature fault, Output phase
loss fault, Earth (Ground) fault, External fault, Charging fault, Current sensor fail fault, EEPROM fault,
4~20mA reference missing fault, Auto tuning fault, Emergency stop, Communication loss, Output unbalance
current fault.
Smooth Operation
Speed Search, Auto Restart and Power Loss Carry Through functions, Heat sink over temperature alarm,
KEB (kinetic energy buffering)
Fault history
Last ten faults with status and eight operational parameters like output frequency, output current, dc bus
voltage and heat sink temperature, Input voltage, Total ON Time, kWH, MWH.
E
n
v
ir
o
n
m
e
n
t
Installation location
Indoor
Vibration
As per EN 60068-2-6, Acceleration: 1g, Frequency: 10 Hz ~ 150 Hz
Ambient temperature
0~50°C (32 ~ 122°F), Open chassis module from 400 kW onwards
Storage temperature
-20°C (-4°F) ~70°C (158°F)
Altitude (above sea level) 1000 m (3300 ft) without derating, above this derate 5% per 305 m (1000 ft)
Humidity
0~95% maximum non-condensing
Enclosure
IP00
Consult Amtech for the details on models AMT-011-X to AMT-030-X
The input power factor is 0.9 with 3% ACL
The inverter efficiency will be >98%
Note1
: Indicates the total effective value including the higher harmonics
Note2
: The maximum applicable motor output is given for a standard induction motor.
Note3
: If the default carrier frequency is exceeded, derate the output current by 5% per 1 kHz as the reduced rating.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...