MODE-H: APPLICATION SPECIFIC FUNCTIONS
No.
Parameter
Unit
Def
Min
Max
Res
Description
WP
GROUP-1: MULTI-PUMP FUNCTION PARAMETERS
H101
No Of Pump
Selection
0
0
4
1
Select number of pumps to be controlled.
H102
Pump Start Hold
Time
Sec
60.0
0.1
3600.0
0.1
If the PID output reaches to upper limit and
remains there for more than the set time, the
next pump will be switched ON.
H103 Pump Stop Hold
Time
Sec
60.0
0.1
3600.0
0.1
If the PID output reaches to lower limit and
remains there for more than the set time, the
next pump will be switched OFF.
H104 Pump Continuous
ON Time Limit
Hrs
8
2
168
1
If pump’s ON/OFF control is not carried out for
more than the set time, the pump will change to
the longest operating pump to the shortest
operating pump.
H105 Pump Changeover
Time
Sec
3
1
120
1
Set the time for changing from the pump that
has been operating longest to the pump
operating shortest.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...