![Amtech Axpert-Eazy AMT-011-4 Instruction Manual Download Page 39](http://html1.mh-extra.com/html/amtech/axpert-eazy-amt-011-4/axpert-eazy-amt-011-4_instruction-manual_2937000039.webp)
Axpert-Eazy
AC Variable Frequency Drive
5.1
5
CHAPTER-5: CONTROL INPUT / OUTPUT TERMINALS
5-1 Input / output terminal functions of PCA-2014A (Control Unit)
TB1
TB2
K1
Fault Relay
K2
Prog Relay-1
K3
Prog Relay-2
+
JP3
LD
JP5
NLD
L
D
N
L
D
VIEW OF PCA-2014A
P15
0V
VIN
FSV
FSI
IIN
0V
VO2
VO1
IO1
CANH RUN
PSI6
COM
0V
IO2
CANL STOP +24V
PSI1
PSI3
PSI5
PSI2
PSI4
+24V PSO1
COM PSO2 PSO4
TX
COM
PBN
PAN
COM
PSO3 COM
RX
PB
PA
+5V
FA
FC
FB
R1A
R1C
R1B
R2A
R2C
R2B
JP1
S
O
U
R
C
E
S
IN
K
SYMBOL
NAME
USE
+24V
+24V source
This source is used for the Programmable Sequence Inputs. The logic for
the Programmable Sequence Inputs can be changed to sink or source with
the help of
JP1
on the control board.
COM
RUN
RUN command
This is programmable sequence input and can be configured to different
functions using
C114
.
STOP
STOP command This is programmable sequence input and can be configured to different
functions using
C115
.
PSI1-6
Programmable
Sequence Inputs
1 ~ 6
These are programmable sequence inputs and can be configured to
different functions using
C101 ~ C106
.
PSO1-4
Programmable
Sequence
Outputs 1 ~ 4
These are programmable sequence outputs and can be configured to
different functions using
C107 ~ C110
.
P15
+15V source
This is a 10V source used when a frequency setter is connected to the
FSV input circuit. The frequency setter to be used should be a variable
resistor of 2k and 2W.
0V
Common
This is a common terminal for analog input signals.
FSV
Frequency
Setting Voltage
input
This is mainly used for setting the frequency (speed) input. A maximum
frequency setting is available at 10V input. This setting is valid when FSV
0-10V, FSV 0-5V, FSV 10-0V or FSV 5-0V is selected as frequency
reference input in
A106
or
D204
or torque reference input in
A108
. Also,
this input can be configured as PID Reference input (
C603
) or PID
Feedback input (
C604
) or Math Reference Input2 (
A702
) or Variable bias
(
A706
) for math operation.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...