Amtech
6-12
6
No.
Parameter
Unit
Def
Min
Max
Res.
Description
WP
B302 Adjustable Over
Current Level
%
300
50
300
1
Set the upper current level as a percentage of
motor rated current. When set to 300%, this
feature is disabled.
B303 Acceleration
Current Limit
%
150
50
200
1
Set the upper current limit as a percentage of
motor rated current for Acceleration.
B304 Under Current
Level
%
0
0
90
1
Set the lower current level as a percentage of
motor rated current for running condition.
B305 Overload Setting
%
105
50
105
1
This is reference for timed overload
characteristic. The inverse time characteristics
will change with change in
B305.
This overload setting for Heavy Duty.
100
50
100
This overload setting for Normal Duty.
B306 Earth Fault
detection Level
%
50
0
100
1
This parameter sets the earth fault detection
level.
B307 DC Bus Voltage
Control
1
1
3
1
When enabled, it will prevent the overvoltage
during RUN condition.
=1: Disable
=2: Frequency Increase
=3: Stop Deceleration
B308 Reverse Direction
Lock
0
0
1
1
Set this to prevent unintentional reverse
direction operation. When enabled, ensure that
forward direction is selected in
A305
(or at
terminal).
The AC DRIVE will not start
otherwise.
=0: Disable
=1: Enable
B309 Change Password
0
0
9999
1
User can change the 4-digit user password for
parameter lock.
B310 Parameter Lock
0
0
9999
1
User selectable 4-digit password to prevent
unintentional parameter changes from the digital
operation panel.
B311 Default Value Load
0
0
111
1
The current active parameters will be saved to
non-volatile memory.
222
The saved parameters will be fetched from
memory and now the drive will respond to these
parameters.
333
All default values will be loaded excluding C205
to C218 and B202 to B211 as per 60Hz/460V
(US standard).
444
All default values will be loaded excluding C205
to C218 and B202 to B211 as per 50Hz/415V.
555
When set to 555, the fault history buffer is
cleared. No previous fault codes and related
parameters will be available.
666
All the user parameters will be set to default
including C205 to C218 and B202 to B211 as
per 50Hz/415V.
777
All the PLC parameters will be set to default.
Note:
The value entered in this parameter will not be memorized. It correct value is entered, appropriate action will be taken
and “00” will be displayed. If incorrect value is entered, no action will be taken and “00” will be displayed.
B312 0Hz Overload
Setting
%
105
0
B313
1
For the self-cooling type motor, when operating
at low speed, set these parameters to meet the
motor characteristics.
B313 0.7*BF Overload
Setting
%
105
0
B305
1
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...