5.2
5
FSI
Frequency
Setting Current
input
This is mainly used for setting the frequency (speed) input. A maximum
frequency setting is available at 20mA input. This setting is valid when FSI
0-20mA, FSI 4-20mA, FSI 20-0mA or FSI 20-4mA is selected as frequency
reference input in
A106
or
D204
or torque reference input in
A108
. Also,
this input can be configured as PID Reference input (
C603
) or PID
Feedback input (
C604
) or Math Reference Input2 (
A702
) or Variable bias
(
A706
) for math operation.
IIN
Current Input
This is mainly used for setting the frequency (speed) input. A maximum
frequency setting is available at 20mA input. This setting is valid when IIN
4-20mA is selected as frequency reference input in
A106
. Also, this input
can be configured as PID Reference input (
C603
) or PID Feedback input
(
C604
) or Math Reference Input2 (
A702
) or Variable bias (
A706
) for math
operation.
VIN
Voltage Input
This is mainly used for setting the frequency (speed) input. A maximum
frequency setting is available at 10V input. This setting is valid when VIN
0-10V is selected as frequency reference input in
A106
. Also, this input
can be configured as PID Reference input (
C603
) or PID Feedback input
(
C604
) or Math Reference Input2 (
A702
) or Variable bias (
A706
) for math
operation.
VO1
Vout-1
These are programmable analog voltage outputs 0-10V. In default
condition, output frequency signal is assigned to VO1 and output current
signal is assigned to VO2. Different seven internal signals can be
assigned to these outputs using
C201
&
C202
.
VO2
Vout-2
IO1
Iout-1
These are programmable analog current outputs 4-20mA. In default
condition, motor power signal is assigned to IO1 and output voltage signal
is assigned to IO2. Different seven internal signals can be assigned to
these outputs using
C203
&
C204
.
IO2
Iout-2
TX
DATA+
These two signals are for the two-wire RS-485 serial link. The protocol
used is Modbus-RTU.
RX
DATA-
PA
A-Phase Pulses The A-phase positive pulse of encoder is applied at this terminal.
PAN
The A-phase negative pulse of encoder is applied at this terminal.
PB
B-Phase Pulses The B-phase positive pulse of encoder is applied at this terminal.
PBN
The B-phase negative pulse of encoder is applied at this terminal.
+5V
+5V source
This is +5V source for the encoder. The encoder is required only in case
of close loop control mode. Refer chapter-10 for detail on encoder
specification.
FA
Programmable
Fault Relay
Contacts
This is programmable relay and its function is assigned to “Fault”
condition in default. When a programmed condition occurs, the section
FA-FC is closed and the section FB-FC is open. Select from different
options using
C113
.
FC
FB
R1A
Programmable
Relay 1 contacts
This is programmable relay and its function is assigned to “Run” condition
in default. When a programmed condition occurs, the section R1A-R1C is
closed and the section R1B-R1C is open. Select from different options
using
C111
.
R1C
R1B
R2A
Programmable
Relay 2 contacts
This is programmable relay and its function is not assigned to any internal
signal in default. When any function is assigned using
C112
and the
programmed condition occurs, the section R2A-R2C is closed and the
section R2B-R2C is open. Select from different options using
C112
.
R2C
R2B
The control circuit wiring is shown as under. The described precautions must be observed during
wiring. Changing the jumper position
JP1
in PCA-2014A/PCA-2004A
between “SINK” and “SOURCE”
position can change the sequence input between sink logic and source logic. Open cover designated
as “Control Unit” to access this jumper.
The unit is shipped with sink logic.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...