Forward Jog
This is a forward jog command. No need to set extra direction PSI.
(Note: If option 2:JOG or 13:Reverse is selected in any PSI, then
40:Forward Jog PSI is not selected and vice versa).
41
Reverse Jog
This is a Reverse jog command. No need to set extra direction PSI.
(Note: If option 2:JOG or 13:Reverse is selected in any PSI, then
41:Reverse Jog PSI is not selected and vice versa).
42
MBRK Answer
This is a feedback signal from external brake in response to the
external brake command.
The default selection is as under.
TERMINAL
OPTION
NAME
PSI1
2
Jog Select
PSI2
10
Emergency stop
PSI3
11
Fault Reset
PSI4
4
Preset i/p-0
PSI5
5
Preset i/p-1
PSI6
6
Preset i/p-2
RUN
24
RUN
STOP
25
STOP
C107 ~ C110: PSO-1 ~ 4
User can configure four programmable sequence outputs for different functions using parameters
C107 ~ C110
. The status of the
Programmable Sequence Output
can be monitored in
M308
. The
various options are explained as under.
OPTION
NAME
FUNCTION
1
Not Used
No function is selected.
2
Run
This turns ON during running, jogging or DC braking.
3
Local
This turns ON when the operation mode is local (operation from the
digital operation panel is selected).
4
Reverse Run
This turns ON when the motor is reverse running.
5
I-Detection
This turns ON when the output current reaches the programmed I-
Detection Level
C302
or higher.
6
Freq Attain
This turns ON when the output frequency (speed) reaches the set
frequency (speed). The detection reach width is set with frequency
attainment detection width
C301
.
7
Speed Detect1
This turns ON when the output frequency (speed) value reaches a speed
higher than the speed set with the detection level –1.
8
Speed Detect2
This turns ON when the motor speed reaches a speed higher than that
set in the detection level-2.
9
Acceleration
This turns ON during acceleration.
10
Deceleration
This turns ON during deceleration.
11
Aux Drive
This turns ON when the auxiliary drive parameter setting is validated by
the sequence input AUXDV.
12
Timer Output
This turns ON during running, jogging, pre-excitation and DC braking. A
programmable off delay (
C309
) is provided, so even if the above
operations turn OFF, this control will not turn OFF for programmed time.
This is used for external fan/ motor control.
13
Zero Speed
This turns ON when the output frequency (speed) value is below the
level set with zero speed level.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...