Axpert-Eazy
AC Variable Frequency Drive
6-79
6
14
Fault Alarm
This output is ON when minor fault alarm is detected.
15
PID Up Limit
The output will be activated when the PID output reaches to the
programmed upper limit value.
16
PID Lo Limit
The output will be activated when the PID output reaches to the
programmed lower limit value.
17
Temp Alarm
The output is ON when the heat sink temperature exceeds the set
Temperature Alarm Level in C311
18
Ready
The output is ON when the unit is ready to start. The soft charge
contactor is energized and no fault condition persists.
19
Pump-1
This is applicable to Multi-pump function only. The output turns ON,
when the respective pump is ON.
20
Pump-2
21
Pump-3
22
Pump-4
23
Doff-End Alarm
This turns ON only at the point going back the set time (
E105
) from the
moment auto stop occurs after completion of the final step when
performing spinning frame operation.
24
Sleep Mode
This turns ON when the unit is in sleep mode.
25
Fault
The output is ON when fault occurs.
26
PLC Output 1
Option 26~32 are use to write PSO status from In-built PLC to Inverter.
This is explained in In-built PLC Function explanation.
27
PLC Output 2
28
PLC Output 3
29
PLC Output 4
30
PLC Output 5
31
PLC Output 6
32
PLC Output 7
33
PID F/B ULmt
The output will be activated when the PID feedback reaches to the
programmed upper limit value.
34
PID F/B LLmt
The output will be activated when the PID feedback reaches to the
programmed lower limit value.
35
FAN Control
The output is ON when the heat sink temperature exceeds the set
temperature level in C315.
The output is OFF when the heatsink temperature goes below the set
level in C315 minus the set hysteresis level in C316.
Once the output is ON then remains ON for 10 minute even if the above
condition is satisfied or not.
36
Ready1
This option is for common dc application. Ready1 will be on 3 seconds
after soft charge operation. This will make sure that the capacitors are
charged to the fullest level. The PSI37: Ready1 feedback will be required
in this case. It will turn off and turn on the Ready1 PSO at every 3
seconds, If the feedback is not available.
37
MBRK
Outputs an external brake command.
38
KEB ON
The output will be on when the KEB function is activated.
39
STO Feedback
The output will be on when STO function is activated (Hard link is not
connected if this function is selected in any PSI).
40
Panel Temp
Alarm
This output will be on if the panel inside temperature > C324 - 5. Output
will be off if panel inside temperature < C324 – 7.
The default setting of the programmable sequence outputs are as under.
TERMINAL
OPTION
NAME
PSO1
2
Run
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...