Amtech
6-46
6
Parameter Value = 50 x Desired rpm / Set output frequency
Suppose a line speed of 273 is to be displayed when the output is 90 Hz.
Parameter Value = 50 X 273 / 90 = 151.667 = 152
Now, at 90Hz the motor speed
M102
will show (152 X 90 / 50) i.e. 274 rpm.
A106: Frequency Reference Input
This parameter can be used to select the speed reference input to the AC DRIVE. The speed
reference can be independently selected from the given options even if the AC DRIVE is controlled
from any of three sources, i.e. Local (Digital Operation Panel), Terminal or Serial. The different
frequency reference inputs are explained as under. The minimum and maximum limits are decided by
A102
and
A103
respectively in all the options.
1. Local
When this option is selected, the set frequency
M105
corresponds to local set frequency
A101
. Use
Digital Operation Panel (keypad) to change the set value. The monitor mode parameter
M105
shows
the value of local set frequency
A101
and
M106
will show keypad as frequency reference input.
The
local set frequency A101 will not have any effect in other options.
2. FSV 0-10V
When this option is selected, the set frequency
M105
corresponds to analog input FSV. The output
frequency will be minimum at 0 V and maximum at 10 V.
A103
A102
10V
F
V
A103
20mA
F
I
4mA
FSV 0-10V
FSI 4-20mA
A102
3. FSI 4-20mA
When this option is selected, the set frequency
M105
corresponds to analog input FSI. The output
frequency will be minimum at 4 mA and maximum at 20 mA.
4. FSV 0-5V
When this option is selected, the set frequency
M105
corresponds to analog input FSV. The output
frequency will be minimum at 0 V and maximum at 5 V.
5. FSI 0-20mA
When this option is selected, the set frequency
M105
corresponds to analog input FSI. The output
frequency will be minimum at 0 mA and maximum at 20 mA.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...