Axpert-Eazy
AC Variable Frequency Drive
6-15
6
No.
Parameter
Unit
Def
Min
Max
Res.
Description
WP
V/F
CL
VEC
OL
VEC
CL
B620 ASR Gain
Change
Frequency 1
Hz
4.00
0.00
600.00
0.01 ASR Gain Change (lower)
Frequency 1. It should be <
B621.
B621 ASR Gain
Change
Frequency 2
Hz
8.00
0.00
600.00
0.01 ASR Gain Change (higher)
Frequency 2. It should be >
B620.
B622 Speed LPF Time
Constant 2
ms
50.0
4.0
1000.0
0.1
Speed feedback low pass filter
Time constant 2 for lower
frequency (below B620).
B623 Encoder LPF
Time Constant
mS
8
0
100
1
Encoder low pass filter time
constant.
B624 ASR
Regenerative
Torque Limit 2
%
20.0
0.1
100.0
0.1
Regenerative torque limit 2.
B625 ASR
Regenerative
Torque Limit 3
%
10.0
0.1
100.0
0.1
Regenerative torque limit 3.
B626 Speed Deviation
Fault Judgment
Time
Sec
10.0
0.1
20.0
0.1
Set the time for judging speed
deviation fault.
B627 Field Weakening
Gain
1.00
0.10
2.00
0.01 Field Weakening Gain. If hunting
occurred in speed in field
weakening region, decrease
gain.
GROUP-7: VECTOR CONTROL CONSTANTS-2
B701 Torque Mode
Selection
0
0
1
1
This parameter will select the
torque control mode.
=0: Disable =1: Enable
B702 Excitation
Current
Reference
%
35
15
100
1
Excitation Current Set value
B703 Torque LPF Time
constant
ms
0.0
0.0
1000.0
0.1
Torque reference low pass filter
Time constant
B704 ACR Kp
0.45
0.01
100.00
0.01 Proportional gain for speed
regulator
B705 ACR Ti
ms
0.40
0.01
300.00
0.01 Integral time constant for speed
regulator
B706 ACR Q Upper
Lmt
%
100.0
0.0
150.0
0.1
ACR Q-Controller output upper
limit
B707 ACR Q Lower
Lmt
%
100.0
0.0
150.0
0.1
ACR Q-Controller output lower
limit
B708 ACR D Upper
Lmt
%
100.0
0.0
150.0
0.1
ACR D-Controller output upper
limit
B709 ACR D Lower
Lmt
%
100.0
0.0
150.0
0.1
ACR D-controller output lower
limit
B710 Torque reference
Polarity
%
0
0
1
1
This is used to select Torque
reference polarity.
=0: Unipolar
=1: Bipolar
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...