4.7
4
2) B201 = 3: Rotational mode (Execution time: approx. 1 minute)
Applicable mode
Parameter No
Name
B201 = 3
Rotational
(Belt OFF)
B202 , B203
R1 : Primary (stator) resistance
B204 , B205
R2’ : Secondary (rotor) resistance
B206 , B207
L
σ
: Leakage inductance
B208 , B209
M' : Excitation (magnetizing) inductance
A501, D301
Manual torque boost
B702
Excitation Current Reference
B118
No Load Output Current
B108
No Load Output Voltage
The motor is rotated and the basic parameters for vector control are automatically adjusted.
3) B201 = 4: Extended Rotational mode (Execution time: approx. 2 minute)
Applicable mode
Parameter No
Name
B201 = 4
Extended
Rotational
(Belt OFF)
B202 , B203
R1 : Primary (stator) resistance
B204 , B205
R2’ : Secondary (rotor) resistance
B206 , B207
L
σ
: Leakage inductance
B208 , B209
M' : Excitation (magnetizing) inductance
A501, D301
Manual torque boost
B702
Excitation Current Reference
B118
No Load Output Current
B809 ~ B816
M variable compensation table
When carrying out constant output operation, the fluctuation compensation for the excitation
inductance is adjusted in this mode, however, the motor will rotate to the maximum speed during
automatic tuning, so special attention must be paid to safety.
Abnormal completion of automatic tuning
- If automatic tuning ends abnormally, the "FLT" LED will turn ON and the display will blink with the
message “Auto Tune Abnormal”.
- Investigate and check according to the error codes.
- In case of error, the error code will be displayed in addition to the progress at the time of error. For
example, if the error comes at 50% progress with an error code 12, then M303 will display 125. The
first two digits display the auto tune error code.
Error code during automatic tuning
Error Code Significance of error code
01
Problem in current sensor circuit, may be loose connection, faulty current sensors,
wrong sensors used.
03
04
Over current condition has occurred during the auto tuning process.
12
Under voltage condition has been detected during the auto tuning process.
The other error codes are for internal diagnosis and debugging purpose.
4-4 Test operations
When finished with automatic tuning, test run the isolated motor, and make sure that there are no
errors.
Use Digital Operation Panel mode to test run the motor. Initially set 10.0Hz and press “RUN” key to
start the motor.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...