46. READ_MON_PARA (OPCODE
050)
This command is used to read the monitor parameter value into the selected Register Number.
Example,
READ_MON_PARA Rn ModId
Where,
Rn = Register Number (0 to 85)
ModId = Modbus Id of Monitor Parameter (0 to 115)
Reference: Serial guide Manual
Example,
to read parameter M104, Output Current ‘s Modbus id is 40004. So
ModId = 40004 – 40001 = 3
47. READ_STA_BIT (OPCODE
051)
This command is used to read bit status of Status Register in selected Flag Number.
Example,
READ_STA_BIT Fn StsRegNo BitNo
Where,
Fn = Flag number (0 to 99)
StsRegNo
.
= Status Register Number (1 to 2)
BitNo. = Bit Number (0 to 15)
48. READ_FLT_BIT (OPCODE
052)
This command is used to read bit status of Fault Code Register in selected Flag Number.
Example,
READ_FLT_BIT Fn FltRegNo BitNo
Where,
Fn = Flag number (0 to 99)
FltRegNo
.
= Fault code Register Number (1 to 5)
BitNo. = Bit Number from (0 to 15)
49. READ_CWORD_BIT (OPCODE
053)
This command is used to read bit status of Control Word Register in selected Flag Number.
Example,
READ_CWORD_BIT Fn CwordRegNo BitNo
Where,
Fn = Flag number (0 to 99)
CwordRegNo = Control Word Register Number (1 to 2)
BitNo. = Bit Number from (0 to 15)
50. WRITE_AN_O/P (OPCODE
054)
This command is used to set Analog Output or Analog Input by the use of selected Register value.
Register value should be in the range of 0 to 1000d. Where 0d will give 0Volt and 1000d will give
10Volt.
Example,
WRITE_AN_O/P PLCAOPn Rn
Where,
PLCAOPn = PLC analog output number (PLCAOP1 to PLCAOP4).
Rn = Register Number (0 to 114).
FOR ANALOG OPUTPUT:
Analog output will come according to selection of
C201
to
C204
.
To get PLC analog output at
VO1
terminal, one of the selectable options from
8:PLC A-O/P 1
to
11:PLC A-O/P 4
should be set at
C201
.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...