Axpert-Eazy
AC Variable Frequency Drive
6-5
6
WP:
Indicates that this parameter is Write Protected during RUN condition.
MODE-A Parameter
No.
Parameter
Unit
Def
Min
Max
Res.
Description
WP
GROUP-1: FREQUENCY SETTING
A101 Local Set
Frequency
Hz
10.00
0.00
600.00
0.01 This is the frequency set from Digital Operation
Panel (
LCD
Keypad Module).
A102 Minimum
Frequency
Hz
0.10
0.00
600.00
0.01 These two parameters are used to configure
Minimum and Maximum Frequency of the AC
DRIVE.
A103 Maximum
Frequency
Hz
50.00
0.10
600.00
0.01
A104 Jog Frequency
Hz
5.00
0.00
600.00
0.01 This is frequency setting for jog input.
A105 Line Speed Setting
1500
0
3000
1
RPM
line speed display. The entered value will
be displayed as motor speed in
M102
at 50Hz in
open loop v/f mode. It will not have any effect in
vector control
modes.
A106 Frequency
Reference Input
1
1
18
1
This is used to select the speed reference.
=1: Local
=3: FSI 4-20mA
=5: FSI 0-20mA
=7: FSI 20-4mA
=9: FSI 20-0mA
=11: Serial
=13: VIN 0-10V
=15: PLC A-O/P 1
=17: PLC A-O/P 3
=2: FSV 0-10V
=4: FSV 0-5V
=6: FSV 10-0V
=8: FSV 5-0V
=10: Static pot
=12: PID Output
=14: IIN 4-20mA
=16: PLC A-O/P 2
=18: PLC A-O/P 4
A107 Local Set Torque
%
0.0
-200.0 200.0
0.1
This is set torque from the operation panel in
vector
control
mode.
A108 Torque Reference
Input
1
1
18
1
This is used to select the torque reference in
vector control
mode.
=1: Local
=3: FSI 4-20mA
=5: FSI 0-20mA
=7: FSI 20-4mA
=9: FSI 20-0mA
=11: Serial
=13: VIN 0-10V
=15: PLC A-O/P 1
=17: PLC A-O/P 3
=2: FSV 0-10V
=4: FSV 0-5V
=6: FSV 10-0V
=8: FSV 5-0V
=10: Static pot
=12: PID Output
=14: IIN 4-20mA
=16: PLC A-O/P 2
=18: PLC A-O/P 4
A109 Extended
Parameter
0
0
1
1
This will enable to display mode D, mode E,
mode G, mode H and mode P.
=0: Disable
=1: Enable
A110 Frequency
Reference Select 1
3
1
18
1
This is used to select the speed reference using
Ref Select 0 & Ref Select 1 through PSI. Refer
description for selection detail.
A111 Frequency
Reference Select 2
10
1
18
1
=1:Local
=3:FSI 4-20mA
=5:FSI 0-20mA
=7:FSI 20-4mA
=9:FSI 20-mA
=11:Serial
=13:Vin 0-10V
=15: PLC A-O/P 1
=17: PLC A-O/P 3
=2:FSV 0-10V
=4:FSV 0-5V
=6:FSV 10-0V
=8:FSV 5-0V
=10:Static Pot
=12:PID Output
=14:Iin 4-20mA
=16: PLC A-O/P 2
=18: PLC A-O/P 4
A112 Frequency
Reference Select 3
11
1
18
1
A113 Stop Frequency
1.00
0.1
600.00 0.01
During deceleration drive act as coast to stop at
this frequency.
GROUP-2: ACCELERATION / DECELERATION TIME
A201 Acceleration Time-
1
Sec
10.0
0.1
6000.0
0.1
Time needed to change the output frequency
from zero to maximum.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...