![Amtech Axpert-Eazy AMT-011-4 Instruction Manual Download Page 42](http://html1.mh-extra.com/html/amtech/axpert-eazy-amt-011-4/axpert-eazy-amt-011-4_instruction-manual_2937000042.webp)
Amtech
5.4
5
5-4 Programmable analog output (PAO) wiring
VO1
VO2
0V
L<30m (98.4')
IO2
Ground
270R
270R
IO1
50R
50R
Output Frequency
Output Current
Output Power
Output Voltage
(0-10V)
(0-10V)
(4-20mA)
(4-20mA)
Precautions
1. Use 10V full-scale meter (impedance 10k or higher).
2. The maximum output current is 1mA for voltage output.
3. Use a shielded wire shorter than 30meters (98.4’) for the wiring.
4. For the shield connections, open the mate side, and connect to 0V terminal on TB1.
5-5 Programmable sequence output (Open Collector Type) wiring
PSO
L<50m (164')
COM
COIL
Max 30Vdc/
50mA
Precautions
1. To drive an L load, such as a coil, insert the flywheel diode shown in the drawing.
2. Keep the wiring length to 50meters (164’) or less.
3. Use within the 30VDC, 50mA ratings range.
Summary of Contents for Axpert-Eazy AMT-011-4
Page 2: ...Amtech ii...
Page 19: ...Axpert Eazy AC Variable Frequency Drive 2 11 2 400V Series AMT 200 4 AMT 250 4...
Page 22: ...Amtech 2 14 2 This Page is intentionally left blank...
Page 37: ...Axpert Eazy AC Variable Frequency Drive 4 9 4...
Page 38: ...Amtech 4 10 4 This page is intentionally left blank...
Page 46: ...Amtech 5 8 5 This page is intentionally left blank...
Page 216: ...Amtech 13 6 13 This page is intentionally left blank...
Page 221: ...Axpert Eazy AC Variable Frequency Drive A 5 13 A Outline Dimensions...
Page 239: ...Notes...
Page 240: ...Notes...
Page 241: ......
Page 242: ...AMTECH...