MODEM COMMUNICATION TO ABB RELAYS
Page 7 of 47
Additionally, Figures 14 and 15 illustrate a communication cable configuration when a Modicon PLC is
connected to a Modem (as is the case when it is using a Ladder Logic XMIT block allowing the port to
operate as a host device).
IED Cable
Male Cable Gender
( 9 Pin Connector)
Modem Cable
Male Cable Gender
(25 Pin Connector)
DTE
DCE
2
3
5
3 RCD
2 TXD
7 GND
8 CD *
4 RTS *
5 CTS *
6 DSR *
20 DTR *
RCD
TXD
GND
(Signal Flow Direction Denoted By Arrow)
*OPTIONAL
DEPENDENT ON
MODEM CONTROL
LINE CONFIGURATION
Figure 6. Example Cable 1: GPU2000R, TPU2000, TPU2000R, DPU2000, DPU2000R,
MSOC, or DPU1500R. It is recommended that DSR, CD, and CTS control be disabled via
modem. If control is disabled, jumpers are optional as shown.
PONI -R
Female Cable Gender
( 9 Pin Connector)
Modem Cable
Male Cable Gender
(25 Pin Connector)
DTE
DCE
2
3
5
7
8
3 RCD
2 TXD
7 GND
4 RTS
5 CTS
6 DSR *
20 DTR *
RCD
TXD
GND
RTS
CTS
(Signal Flow Direction Denoted By Arrow)
*OPTIONAL
DEPENDENT ON
MODEM CONTROL
LINE CONFIGURATION
Figure 7. Example Cable 2: ABB PONI R (installed in a REL 301, 302, 350, 352, 356 or
MDAR), using hardware handshaking configured in the modem. Install optional jumper if
modem configured for supplying DSR signal.
PONI -R
Female Cable Gender
( 9 Pin Connector)
Modem Cable
Male Cable Gender
(25 Pin Connector)
DTE
DCE
2
3
5
7
8
3 RCD
2 TXD
7 GND
6 DSR *
20 DTR *
RCD
TXD
GND
RTS
CTS
(Signal Flow Direction Denoted By Arrow)
*OPTIONAL
DEPENDENT ON
MODEM CONTROL
LINE CONFIGURATION
Figure 8. Example Cable 3: ABB PONI R (installed in a REL 301, 302, 350, 352, 356 or
MDAR), NOT using hardware handshaking configured in the modem. Install optional
jumper if modem configured for supplying DSR signal.
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...