ABB REL 356 Current Differential Protection
2-15
Installation, Operation and Maintenance
Table 2-3. Monitoring Functions
Function
Description
Format
Units
CHRX
REL 356 channel receive status
NORM/OPBR/DSBL/CHTB
CHTX
REL 356 channel transmit status
NORM/OPBR/DSBL
IA
IA metered current magnitude
XXX.X
Amps
Ð
IA
IA metered current angle
XXXX
deg
VAG
VAG metered voltage magnitude
XXX.X
volts
Ð
VAG
VAG metered voltage angle
XXXX
deg
IB
IB metered current magnitude
XXX.X
Amp
Ð
IB
IB metered current angle
XXXX
deg
VBG
VBG metered voltage magnitude
XXX.X
volts
Ð
VBG
VBG metered voltage angle
XXXX
deg
IC
IC metered current magnitude
XXX.X
Amps
Ð
IC
IC metered current angle
XXXX
deg
VCG
VCG metered voltage magnitude
XXX.X
volts
Ð
VCG
VCG metered voltage angle
XXXX
deg
3I0
3I0 metered current magnitude
XXX.X
volts
Ð
3I0
3I0 metered current angle
XXXX
deg
DATE
Date (month, day)
MM.DD
TIME
Time (hours, minutes)
HH.MM
SET
Setting access status
BOTH/LOC/REM
LOP
Loss-of-potential indication
YES/NO
LOI
Loss-of-current indication
YES/NO
OSB
Out-of-step blocking indication
YES/NO
MLDT
Measured local delay time from Modem/CODEC
XXX.X/FAIL
msec
*XMTR
Channel transit level
XXXX
dBm
*RCVR
Channel receive level
XXXX
dBm
*SNR
Channel signal-to-noise ratio
XXXX
dB
**FEPH
Channel Error
Value/SYER/CTER/IDER
NOTE:
All angles are computed using VAG as the reference angle.
*
9600 bps audio tone option
**
56/64 kbps digital communication option
IT
IT composite current magnitude
XXX.X
Amps
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...