LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY
Page 21 of 53
Figure 35. Segment 3 Network 6 - XMIT Dwell Timer and Bad Transmission Counter
Logic
Segment 3 Network 7:
As with the Modbus Plus MSTR Logic, another FIFO has been constructed in which a manual control (or
automated control instruction initiated by the ladder logic may be performed). Note the FIFO may
contain up to 19 control instructions which may be queue’d for processing. Additionally, note the trigger
construct for pending FIFO commands to be sent to the XMIT block (coil 00309) interrupting the cyclical
poll. Using this philosophy ensures that control commands and operator initiated commands are
immediately scheduled for operation by the XMIT block.
Figure 36. Segment 3 Network 7 – FIFO Empty/Full Notification Logic
Segment 3 Network 8:
If the FIFO has data, this logic construct interrupts the polling of the XMIT instructions and immediately
parameterizes the block with the parameters pointed to within the FIFO queue. A dwell time of 100 mS
creates a pause for the XMIT instruction to terminate. The logic in SEGMENT 3 NETWORK 9 creates the
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...