ABB REL 356 Current Differential Protection
5-24
Testing
Out Of Step System Functional Tests
For systems equipped with OST logic the following settings may be used to check the OST logic in REL 356:
NOTE: These tests are optional and require programing Computer Aided, Multi-amp or Doble test equipment.
In the R-X diagram, the positions shown correspond to the following quantities:
PANG = 65
GANG = 65
ZR
= 3.0
BKUP = OUT
LOPB
= NO
FDOP = IN
FDOG = IN
DIRU
= ZSEQ
IOM
= 0.5
TOG
= BLK
Z2P
= 8.5
T2P
= 0.1
Z2GF
= 6.5
Z2GR
= 0.01
T2G
= 0.1
Z3P
= 11.0
T3P
= .2
Z3GF
= 11.0
Z3GR
= 0.01
T3G
= .2
OST
= WAYO
OSB
= BOTH
RT
= 2.0
RU
= 4.0
OST1
= 2
OST2
= 3
OST3
= 3
OSOT = 100
1
2
3
4
5