LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY
Page 33 of 53
Figure 64. Segment 4 Network 4 - MAGELIS Pushbutton Manual Trip Logic
Segment 4 Network 5
If the control key for a MANUAL CLOSE of the DPU is depressed on the MMI, this logic construct loads
the FIFO with the XMIT pointer commands 22,20 to perform a breaker trip operation on the DPU2000R.
Bit 13 of Register 40051 is set by the MMI to trigger this instruction (SENS). The ladder Logic is
illustrated in Figure 65.
Figure 65. Segment 4 Network 5 - MAGELIS Manual Close Pushbutton Logic
Segment 4 Network 6
If the control key for a MANUAL TRIP of the PCD is depressed on the MMI, this logic construct loads the
FIFO with the XMIT pointer commands 26,31 to perform a breaker trip operation on the DPU2000R. Bit
11 of Register 40051 is set by the MMI to trigger this instruction (SENS).