LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY
Page 32 of 53
Figure 62. Segment 4 Network 2 - MAGELIS F1 and F2 Function Key LED Control Auto
Manual Control Logic
Segment 4 Network 3
This network upon the MMI control screen being issues a system reset, the pending control operations,
buffers and latched commands are reset to an initial state.
Figure 63. Segment 4 Network 3 – System Reset Logic
Segment 4 Network 4
If the control key for a MANUAL TRIP of the DPU is depressed on the MMI, this logic construct loads the
FIFO with the XMIT pointer commands 21,20 to perform a breaker trip operation on the DPU2000R. Bit
15 of Register 40051 is set by the MMI to trigger this instruction (SENS). The ladder logic is illustrated in
Figure 64.