ABB REL 356 Current Differential Protection
2-17
Installation, Operation and Maintenance
Table 2-4. Target (Fault Data) Information Continued
DKM
Fault distance in kilometers
XXX.X
km
PFLC
Pre-fault load current
XXX.X
amps
PFLV
Pre-fault voltage
XXX.X
volts
LP
Pre-fault load angle
XXX.X
deg
VAG
VAG fault voltage magnitude
VAG fault voltage angle
XXX.X
XXX.X
volts
deg
VBG
VBG fault voltage magnitude
VBG fault voltage angle
XXX.X
XXX.X
volts
deg
VCG
VCG fault voltage magnitude
VCG fault voltage angle
XXX.X
XXX.X
volts
deg
3V0
3V0 fault voltage magnitude
3V0 fault voltage angle
XXX.X
XXX.X
volts
deg
Target
Description
Format
Units
IA
IA fault voltage magnitude
IA fault voltage angle
XXX.X
XXX.X
amps
deg
IB
IB fault voltage magnitude
IB fault voltage angle
XXX.X
XXX.X
volts
deg
IC
IC fault voltage magnitude
IC fault voltage angle
XXX.X
XXX.X
amps
deg
3I0
3I0 fault voltage magnitude
3I0 fault voltage angle
XXX.X
XXX.X
volts
deg
Notes: The "YES/NO" targets are displayed only if they are "YES". The
impedance is dependent upon the CTYP setting. The internal
impedance values are for a 5A ct. The impedance value is multiplied
by 5 if a 1 A ct is used (CTYP = 1). The angles are not displayed if the
magnitude of the value or the reference is less than 0.5 a or 0.7 rms.
*
**
9600 bps Audio Tone Channel
56/64 kbps Digital Communication
DATE
Date of fault (month.day)
MM.DD
YEAR
Year of fault
YYYY
TIME
Time of fault (hours.minutes)
HH.MM
SEC
Time of fault (seconds)
XXXX
sec
MSEC
Time of fault (milliseconds)
XXXX
msec
LDT
LDT used at the time of trip
XXX.X
msec
XMTR
Channel transmit level
XXXX
dBm
*RCVR
Channel receive level
XXXX
dBm
*SNR
Channel signal-to-noise ratio
XXXX
dB
**FEPH Channel error
XXXX/FAIL
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...