ABB REL 356 Current Differential Protection
3-15
Settings and Application
Zone 2 Phase Reach (Z2P)
This setting coordinates the Zone 2 reach for phase to phase faults and three phase faults. The setting is in secondary
ohms.
Zone 2 Phase Timer (T2P)
Selects the time delay for Zone 2 phase fault detection. When set to zero, Zone 2 should be set underreaching. The
setting is in seconds.
Zone 2 Forward Ground Reach (Z2GF)
This setting controls the forward reach of the Zone 2 ground unit. The setting is in secondary ohms.
Zone 2 Reverse Ground Reach (Z2GR)
This setting controls the reverse reach of the Zone 2 ground unit. The setting is in secondary ohms. The Z2GR setting
is determined by the desired reach along the R-axis.
Zone 2 Ground Timer (T2G)
Selects the time delay for Zone 2 phase fault detection. When set to zero, Zone 2 should be set underreaching. The
setting is in seconds.
Zone 3 Phase Reach (Z3P)
This setting coordinates the Zone 3 reach for phase to phase faults and three phase faults. The setting is in secondary
ohms.
Zone 3 Phase Timer (T3P)
Selects the time delay for Zone 3 phase fault detection. The setting is in seconds.
Zone 3 Forward Ground Reach (Z3GF)
This setting controls the forward reach of the Zone 3 ground unit. The setting is in secondary ohms.
Zone 3 Reverse Ground Reach (Z3GR)
This setting controls the reverse reach of the Zone 3 ground unit. The setting is in secondary ohms.
Zone 3 Ground Timer (T3G)
Selects the time delay for Zone 3 phase fault detection. The setting is in seconds.
Out of Step Settings – Versions with Distance Option only
Current differential protection is immune to power swings. When voltage inputs are part of the REL 356, blinders are
provided for power swing detection. The out of step trip and block logic is provided as part of the distance option. Out of
step block is only enabled when the distance backup protection is switched due to channel trouble or differential block
as determined by the setting BKUP. Out of step trip, when selected, is always active regardless of the BKUP setting.
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...