ABB REL 356 Current Differential Protection
1-5
Product Overview and Specifications
Specifications
Ratings
Nominal ac voltage at 60 Hz
69.3 V rms
Nominal ac current (In)
1 or 5 A rms
Rated frequency
50 or 60 Hz
Maximum permissible ac voltage
Continuous 160 V rms (limited by maximum input to A/D converter)
10 seconds 240 V rms (limited by input transformer flux density)
Maximum permissible ac current
Continuous 3 x nominal current (limited by thermal characteristics)
1 second
Operational 160 A rms at 5 A, 32 A rms at 1 A
(limited by maximum input to the A/D converter)
Thermal 100 x nominal current
dc battery voltages, nominal (range)
60/48 Vdc (30 – 70 Vdc)
110/125 Vdc (88 - 140 Vdc)
220/250 Vdc (176 – 280 Vdc)
dc burdens
normal
15 W
tripping
40 W
ac burdens
volts per phase
0.02 VA at 70 Vac
current per phase
0.45 VA at 5 A
External connections
Terminal blocks located on the rear of the chassis suitable for #14 square tongue lugs. Wiring to FT-14 switches suitable
for #12 wire lugs.
Contact data
Trip contacts
make and carry
1 second
30 A
continuous
10 A
break
resistive
50 W
L/R = 45 msec
25 W
Non-trip contacts
continuous 1 A
resistive interrupt 0.1 A
Contacts meet IEC255-6A, IEC255-12, IEC255-16, BS142-1982
Summary of Contents for REL 356
Page 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Page 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Page 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Page 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Page 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Page 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Page 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...