LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY
Page 35 of 53
Figure 68. Segment 4 Network 8 - MAGELIS TPU Manual Trip Pushbutton Logic
Segment 4 Network 9
The MAGELIS operator interface does not display Floating Point Values. All the mathematics in this
program is performed using floating point math. In order to display the information on the MMI display
(MAGELIS), it must be converted from floating point to integer for display, Kwatts for phases A, B, C, and
loading of the DPU prior to the TPU trip. These values are calculated using floating point math
instructions.
Figure 69. Segment 4 Network 9 - MAGELIS Watt Hour Display in Integer Units
Segment 4 Network 10,11,12
The operator is also able to reset the target information via the MAGELIS MMI. If the unit is in manual
mode, the operator may depress the function key to reset the targets on the TPU (BIT 8 REGISTER
40051) DPU (BIT 10 REGISTER 40051) AND PCD (BIT 6 REGISTER 40051). The ladder logic for these
constructs are listed in Figures 70 through 72.