Communication
54
Format of the PDO mapping (example for drive parameter 12.02)
Note:
The maximum number of I/O parameters that can be
simultaneously mapped for cyclic communication depends on the
drive type and application. For example, ACS800 supports 12
inputs and 12 outputs and ACS550 supports 15 outputs and 15
inputs.
Service Data Objects (SDOs)
Service Data Objects are mainly used for transferring non time-
critical data, e.g. parameter values. EtherCAT® specifies both
SDO services and SDO Information services: SDO services
provide read/write access to the entries in the device CoE Object
Dictionary. SDO Information services allow the Object Dictionary
itself to be read. The services supported by RECA-01 are
described in table
Supported SDO and SDO Information services
below.
Supported SDO and SDO Information services
Type
MSB
LSB
UNIT 32
31
16 15
8 7
0
Description Index
e.g 0×400C (hex)
Drive parameter
group 12 (16 bits)
Sub index
e.g 2 Drive
parameter group 12
(8 bits)
Object length in bits
e.g 0×10 (hex) =
16 bits
(8 bits)
Service
Function
SDO Download Expedited
Writes up to four octets to the slave.
SDO Download Normal
Writes up to a negotiated number of octets to the
slave.
Download SDO Segment
Writes additional data if the object size is greater than
the negotiated number of octets.
SDO Upload Expedited
Reads up to four octets from the slave.
SDO Upload Normal
Reads up to a negotiated number of octets from the
slave.
Upload SDO Segment
Reads additional data if the object size is greater than
the negotiated number of octets.
=
=
Summary of Contents for RECA-01
Page 1: ...ABB Drives User s Manual EtherCAT Adapter Module RECA 01 ...
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 24: ...Quick start up guide 24 ...
Page 26: ...Mechanical installation 26 ...
Page 28: ...Electrical installation 28 ...
Page 32: ...Master configuration 32 ...
Page 56: ...Communication 56 ...
Page 72: ...CoE object dictionary 72 ...
Page 80: ...CoE Error codes 80 ...