Drive configuration
30
The RECA-01 configuration parameters
1 MODULE TYPE
This parameter shows the module type as detected by the drive.
The value cannot be adjusted by the user.
If this parameter is undefined, the communication between the
drive and the module has not been established.
2 TRANSPARENT/PROFILE MODE
This parameter is used for choosing either the transparent (ABB
Drives) or the DSP 402 communication profile. This selection can
also be changed with CoE object 0×2400 (hex).
Par.
no.
Parameter name Alternative settings
Default setting
1
MODULE TYPE
(Read-only)
ETHERCAT
2
TRANSPARENT/
PROFILE MODE
(
0
) Profile mode (DSP 402)
(
1
) Transparent mode
(ABB Drives)
(0)
Profile mode
(DSP 402)