![background image](http://html.mh-extra.com/html/abb/reca-01/reca-01_user-manual_207019.webp)
Quick start-up guide
19
Quick start-up guide
Overview
This chapter presents the steps to take during the start-up of the
RECA-01 EtherCAT® Adapter module.
WARNING!
Follow the safety instructions given in this manual and
the
Hardware Manual
of the drive.
Mechanical installation
• Insert the RECA-01 into its specified slot in the drive (SLOT2 for
ACS550, SLOT1 for ACS800).
• Fasten the two screws.
Electrical installation
• Connect the Ethernet cable (RJ-45 connector) to the RECA-01
module. Standard CAT 5 UTP or STP cables can be used.
Avoid parallel runs with power (e.g. motor) cables.
Summary of Contents for RECA-01
Page 1: ...ABB Drives User s Manual EtherCAT Adapter Module RECA 01 ...
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 24: ...Quick start up guide 24 ...
Page 26: ...Mechanical installation 26 ...
Page 28: ...Electrical installation 28 ...
Page 32: ...Master configuration 32 ...
Page 56: ...Communication 56 ...
Page 72: ...CoE object dictionary 72 ...
Page 80: ...CoE Error codes 80 ...