12.16.6
Operation principle
Insulation liquid monitoring function SSIML (71) is used to monitor oil level in the
circuit breaker. Two binary output signals are used from the circuit breaker to initiate
alarm signals, level below alarm level and level below lockout level. If the input signal
LVL_ALM is high, which indicate that the oil level in the circuit breaker is below
alarm level, the output signal LVL_ALM, level below alarm level, will be initiated
after a set time delay and indicate that maintenance of the circuit breaker is required.
Similarly, if the input signal LVL_LO is high, which indicate oil level in the circuit
breaker is below lockout level, the output signal LVL_LO, will be initiated after a time
delay. The two time delay settings,
tLevelAlarm
and
tLevelLockOut
, are included in
order not to initiate any alarm for short sudden changes in the oil level. If the oil level
in the circuit breaker goes below the levels for more than the set time delays the
corresponding signals, LVL_ALM, level below alarm level and LVL_LO, level below
lockout level alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms and the input signal
BLOCK to block both alarms and the function.
12.16.7
Technical data
Table 263:
SSIML(71) Technical data
Function
Range or value
Accuracy
Alarm, oil level
0.00-25.00
-
Oil level lockout
0.00-25.00
-
Temperature alarm
-40.00-200.00
-
Temperature lockout
-40.00-200.00
-
Timers
(0.000-60.000) s
± 0.5% ± 110 ms
12.17
Circuit breaker condition monitoring SSCBR
12.17.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Circuit breaker condition monitoring
SSCBR
-
-
Section 12
1MRK 505 277-UUS C
Monitoring
318
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...