Name
Values (Range)
Unit
Step
Default
Description
DrepChNoV_A
1 - 30
Ch
1
5
Recorder Input number recording phase
voltage, VA
DrepChNoV_B
1 - 30
Ch
1
6
Recorder Input number recording phase
voltage, VB
DrepChNoV_C
1 - 30
Ch
1
7
Recorder Input number recording phase
voltage, VC
12.13.6
Monitored data
Table 247:
LMBRFLO Monitored data
Name
Type
Values (Range)
Unit
Description
FLT_REL
REAL
-
-
Distance to fault, relative
FLT_DIST
REAL
-
-
Distance to fault in line length
unit
FLT_X
REAL
-
Ohm
Reactive distance to fault
FLT_R
REAL
-
Ohm
Resistive distance to fault
FLT_LOOP
INTEGER
0=---
1=L1-N
2=L2-N
3=L3-N
4=L1-L2
5=L2-L3
6=L3-L1
7=L1-L2-L3
-
Fault loop
12.13.7
Operation principle
The Fault locator (LMBRFLO) in the IED is an essential complement to other
monitoring functions, since it measures and indicates the distance to the fault with high
accuracy.
When calculating distance to fault, pre-fault and fault phasors of currents and voltages
are selected from the Trip value recorder data, thus the analog signals used by the fault
locator must be among those connected to the disturbance report function. The analog
configuration (channel selection) is performed using the parameter setting tool within
PCM600.
The calculation algorithm considers the effect of load currents, double-end infeed and
additional fault resistance.
Section 12
1MRK 505 277-UUS C
Monitoring
302
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...