Name
Type
Description
V1RANG
INTEGER
V1 Magnitude range
V1ANGL
REAL
U1 Angle
V2
REAL
U2 Amplitude
V2RANG
INTEGER
V2 Magnitude range
V2ANGL
REAL
U2 Angle
12.1.6.4
Settings
Table 200:
VMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
3V0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
3V0Min
0 - 2000000
V
1
0
Minimum value
3V0Max
0 - 2000000
V
1
318000
Maximum value
3V0RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
3V0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
3V0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V1Min
0 - 2000000
V
1
0
Minimum value
V1Max
0 - 2000000
V
1
106000
Maximum value
V1RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
V1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2Min
0 - 2000000
V
1
0
Minimum value
V2Max
0 - 2000000
V
1
106000
Maximum value
V2RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
V2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
V2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
1MRK 505 277-UUS C
Section 12
Monitoring
233
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...