The polarizing phasor is used together with the phasor of the operating directional
current, in order to determine the direction to the ground fault (Forward/Reverse). In
order to enable voltage polarizing the magnitude of polarizing voltage shall be bigger
than a minimum level defined by setting parameter
VpolMin
.
It shall be noted that residual voltage (V
n
) or negative sequence voltage (V
2
) is used to
determine the location of the ground fault. This insures the required inversion of the
polarizing voltage within the ground-fault function.
Current polarizing
When current polarizing is selected the function will use an external residual current
(3I
0
) or the calculated negative sequence current (I
2
) as polarizing quantity IPol. The
user can select the required current.
The residual current can be:
1. directly measured (when a dedicated CT input of the IED is connected in PCM600
to the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input I3PPOL). This dedicated IED CT input is then typically
connected to one single current transformer located between power system WYE
point and ground (current transformer located in the WYE point of a WYE
connected transformer winding).
•
For some special line protection applications this dedicated IED CT input
can be connected to parallel connection of current transformers in all three
phases (Holm-Green connection).
2. calculated from three phase current input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) function
analog input I3PPOL is NOT connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I
0
from the first
three inputs into the pre-processing block by using the following formula:
3
= ×
=
+
+
Pol
I
Io
IA IB IC
EQUATION2019-ANSI V1 EN
(Equation 11)
where:
IA, IB and IC are fundamental frequency phasors of three individual phase currents.
The negative sequence current can be calculated from the three-phase current input
within the IED by using the pre-processing block. The pre-processing block will
calculate the negative sequence current from the three inputs into the pre-processing
block by using the following formula:
1MRK 505 277-UUS C
Section 7
Current protection
91
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...