Name
Values (Range)
Unit
Step
Default
Description
AccCurrAlmLvl
0.00 - 20000.00
-
0.01
2500.00
Setting of alarm level for accumulated
currents power
AccCurrLO
0.00 - 20000.00
-
0.01
2500.00
Lockout limit setting for accumulated currents
power
DirCoef
-3.00 - -0.50
-
0.01
-1.50
Directional coefficient for CB life calculation
LifeAlmLevel
0 - 99999
-
1
5000
Alarm level for CB remaining life
OpNumRatCurr
1 - 99999
-
1
10000
Number of operations possible at rated current
OpNumFaultCurr
1 - 10000
-
1
1000
Number of operations possible at rated fault
current
OpNumAlm
0 - 9999
-
1
200
Alarm limit for number of operations
OpNumLO
0 - 9999
-
1
300
Lockout limit for number of operations
tOpenAlm
0 - 200
ms
1
40
Alarm level setting for open travel time
tCloseAlm
0 - 200
ms
1
40
Alarm level setting for close travel time
OpenTimeCorr
0 - 100
ms
1
10
Correction factor for open travel time
CloseTimeCorr
0 - 100
ms
1
10
Correction factor for CB close travel time
DifTimeCorr
-10 - 10
ms
1
5
Correction factor for time difference in
auxiliary and main contacts open time
tSprngChrgAlm
0.00 - 60.00
s
0.01
1.00
Setting of alarm for spring charging time
tPressAlm
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure alarm
TPressLO
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure lockout
AccEnerInitVal
0.00 - 9999.99
-
0.01
0.00
Accumulation energy initial value
CountInitVal
0 - 9999
-
1
0
Operation numbers counter initialization value
CBRemLife
0 - 9999
-
1
5000
Initial value for the CB remaining life estimates
InactDayAlm
0 - 9999
Day
1
2000
Alarm limit value of the inactive days counter
InactDayInit
0 - 9999
Day
1
0
Initial value of the inactive days counter
InactHourAlm
0 - 23
Hour
1
0
Alarm time of the inactive days counter in hours
12.17.6
Monitored data
Table 267:
SSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
CBOTRVT
REAL
-
ms
Travel time of the CB during
opening operation
CBCLTRVT
REAL
-
ms
Travel time of the CB during
closing operation
SPRCHRT
REAL
-
s
The charging time of the CB
spring
NO_OPR
INTEGER
-
-
Number of CB operation cycle
Table continues on next page
1MRK 505 277-UUS C
Section 12
Monitoring
321
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...