Name
Type
Values (Range)
Unit
Description
VALUE4
INTEGER
-
-
Output of counter 4
VALUE5
INTEGER
-
-
Output of counter 5
VALUE6
INTEGER
-
-
Output of counter 6
12.2.7
Operation principle
Event counter (CNTGGIO) has six counter inputs. CNTGGIO stores how many times
each of the inputs has been activated. The counter memory for each of the six inputs is
updated, giving the total number of times the input has been activated, as soon as an
input is activated. The maximum count up speed is 10 pulses per second. The
maximum counter value is 10 000. For counts above 10 000 the counter will stop at 10
000 and no restart will take place.
To not risk that the flash memory is worn out due to too many writings, a mechanism
for limiting the number of writings per time period is included in the product. This
however gives as a result that it can take long time, up to several minutes, before a new
value is stored in the flash memory. And if a new CNTGGIO value is not stored before
auxiliary power interruption, it will be lost. CNTGGIO stored values in flash memory
will however not be lost at an auxiliary power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters at
testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.
All inputs are configured via PCM600.
12.2.7.1
Reporting
The content of the counters can be read in the local HMI.
Reset of counters can be performed in the local HMI and a binary input.
Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.
12.2.8
Technical data
Table 213:
CNTGGIO technical data
Function
Range or value
Accuracy
Counter value
0-10000
-
Max. count up speed
10 pulses/s
-
Section 12
1MRK 505 277-UUS C
Monitoring
250
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...