Table 74:
OV2PTOV (59) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
-
-
PhN DFT
Group selector for connection type
8.2.6
Monitored data
Table 75:
OV2PTOV (59) Monitored data
Name
Type
Values (Range)
Unit
Description
V_A
REAL
-
kV
Voltage in phase A
V_B
REAL
-
kV
Voltage in phase B
V_C
REAL
-
kV
Voltage in phase C
8.2.7
Operation principle
Two step overvoltage protection OV2PTOV (59) is used to detect high power system
voltage. OV2PTOV (59) has two steps with separate time delays. If one-, two- or three-
phase voltages increase above the set value, a corresponding PICKUP signal is issued.
OV2PTOV (59) can be set to PICKUP/TRIP, based on
1 out of 3
,
2 out of 3
or
3 out of
3
of the measured voltages, being above the set point. If the voltage remains above the
set value for a time period corresponding to the chosen time delay, the corresponding
trip signal is issued.
The time delay characteristic is settable for step 1 and can be either definite or inverse
time delayed. Step 2 is always definite time delayed.
The voltage related settings are made in percent of the global set base voltage
VBase
,
which is set in kV, phase-to-phase.
OV2PTOV (59) can be set to measure phase-to-ground fundamental value, phase-to-
phase fundamental value, phase-to-ground RMS value or phase-to-phase RMS value.
The choice of measuring is done by the parameter
ConnType
.
The voltage related settings are made in percent of base voltage which is set in kV phase-
to-phase voltage. OV2PTOV (59) will operate if the voltage gets higher than the set
percentage of the set global base voltage
VBase
. This means operation for phase-to-
ground voltage over:
Section 8
1MRK 505 277-UUS C
Voltage protection
132
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...