The magnitude of the phase-ground voltage has been above
VPPU
for more than
1.5 cycle
•
The magnitude of DV is higher than the setting
DVPU
•
The magnitude of DI is below the setting
DIPU
and at least one of the following conditions are fulfilled:
•
The magnitude of the phase current in the same phase is higher than the setting
50P
•
The circuit breaker is closed (52a = True)
The first criterion means that detection of failure in one phase together with a current
in the same phase greater than
50P
will set the output. The measured phase current is
used to reduce the risk of false fuse failure detection. If the current on the protected
line is low, a voltage drop in the system (not caused by fuse failure) is not necessarily
followed by current change and a false fuse failure might occur.
The second criterion requires that the delta condition shall be fulfilled in any phase
while the circuit breaker is closed. A fault occurs with an open circuit breaker at one
end and closed at the other end, could lead to wrong start of the fuse failure function at
the end with the open breaker. If this is considered to be a disadvantage, connect the
52a input to FALSE. In this way only the first criterion can activate the delta function.
Section 9
1MRK 505 277-UUS C
Secondary system supervision
150
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...