10.1.5
Operation principle
10.1.5.1
Bay control QCBAY
The functionality of the Bay control (QCBAY) function is not defined in the IEC 61850–
8–1 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay for example, switch control
functions, voltage control functions and measurement functions.
Local panel switch
The local panel switch is a switch that defines the operator place selection. The switch
connected to this function can have three positions remote/local/off. The positions are
here defined so that remote means that operation is allowed from station/remote level
and local from the IED level. The local/remote switch is also on the control/protection
IED itself, which means that the position of the switch and its validity information are
connected internally, and not via I/O boards. When the switch is mounted separately
from the IED the signals are connected to the function via I/O boards.
When the local panel switch (or LHMI selection, depending on the set source to select
this) is in Off position, all commands from remote and local level will be ignored. If
the position for the local/remote switch is not valid the PSTO output will always be set
to faulty state (3), which means no possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch, the
function blocks LOCREM and LOCREMCTRL are needed and connected to QCBAY.
Permitted Source To Operate (PSTO)
The actual state of the operator place is presented by the value of the Permitted Source
To Operate, PSTO signal. The PSTO value is evaluated from the local/remote switch
position according to table
. In addition, there is one configuration parameter that
affects the value of the PSTO signal. If the parameter
AllPSTOValid
is set and LR-
switch position is in Local or Remote state, the PSTO value is set to 5 (all), that is, it is
permitted to operate from both local and remote level without any priority. When the
external panel switch is in Off position the PSTO value shows the actual state of switch
that is, 0. In this case it is not possible to control anything.
Section 10
1MRK 505 277-UUS C
Control
164
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...