settable for step 1 and can be either definite or inverse time delayed. Step 2 is always
definite time delayed.
UV2PTUV (27) can be set to measure phase-to-ground fundamental value, phase-to-
phase fundamental value, phase-to-ground true RMS value or phase-to-phase true
RMS value. The choice of the measuring is done by the parameter
ConnType
. The
voltage related settings are made in percent of base voltage which is set in kV phase-to-
phase voltage. This means operation for phase-to-ground voltage under:
(%)
(
)
3
Vpickup
VBase kV
<
×
EQUATION1606 V1 EN
(Equation 25)
and operation for phase-to-phase voltage under:
Vpickup
(%) VBase(kV)
<
×
EQUATION1991-ANSI V1 EN
(Equation 26)
When phase-to-ground voltage measurement is selected the function
automatically introduces division of the base value by the square root
of three.
8.1.7.1
Measurement principle
Depending on the set
ConnType
value, UV2PTUV (27) measures phase-to-ground or
phase-to-phase voltages and compare against set values,
Pickup1
and
Pickup2
. The
parameters
OpMode1
and
OpMode2
influence the requirements to activate the
PICKUP outputs. Either
1 out of 3
,
2 out of 3
, or
3 out of 3
measured voltages have to
be lower than the corresponding set point to issue the corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
8.1.7.2
Time delay
The time delay for step 1 can be either definite time delay (DT) or inverse time
undervoltage (TUV). Step 2 is always definite time delay (DT). For the inverse time
delay two different modes are available; inverse curve A and inverse curve B.
The type A curve is described as:
Section 8
1MRK 505 277-UUS C
Voltage protection
126
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...