Comparator
V<BattVoltLowLim
Comparator
U<BattVoltHiLim
V_BATT
PU_VLOW
PU_VHI
AL_VLOW
AL_VHI
ANSI11000292-1-en.vsd
0-tReset
0
0
0-tDelay
0-tReset
0
0
0-tDelay
ANSI11000292 V1 EN
Figure 124:
Functional module diagram
The battery rated voltage is set with the
RtdBattVolt
setting. The value of the
BattVoltLowLim
and
BattVoltHiLim
settings are given in relative per unit to the
RtdBattVolt
setting.
It is possible to block the function outputs by the
BLOCK
input.
Low level detector
The level detector compares the battery voltage
V_BATT
with the set value of the
BattVoltLowLim
setting. If the value of the
V_BATT
input drops below the set value of
the
BattVoltLowLim
setting, the pickup signal
PU_VLOW
is activated.
The measured voltage between the battery terminals
V_BATT
is available through the
Monitored data view.
High level detector
The level detector compares the battery voltage
V_BATT
with the set value of the
BattVoltHiLim
setting. If the value of the
V_BATT
input exceeds the set value of the
BattVoltHiLim
setting, the pickup signal
PU_VHI
is activated.
Time delay
When the operate timer has reached the value set by the
tDelay
setting, the
AL_VLOW
and
AL_VHI
outputs are activated. If the voltage returns to the normal value before the
module operates, the reset timer is activated. If the reset timer reaches the value set by
tReset
, the operate timer resets and the
PU_VLOW
and
AL_VHI
outputs are deactivated.
1MRK 505 277-UUS C
Section 12
Monitoring
311
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...